Speed Governor
Product Specifications:
PERFORMANCE |
|
Isochronous Operation |
± 0.25%or better |
Speed Range/ Governor |
1 - 7.5kHz Continuous |
Speed Driftwith Temperature |
±1% Maximum |
Idle Adjust Clockwise |
60% of Set Speed |
Idle Adjust Counterclockwise |
Less than 1200 Hz |
Droop Range |
1 - 5% regulation |
Droop AdjustMaximum (K-L jumpered) |
400 Hz ±75 Hz per 1.0 A change |
Droop AdjustMinimum (K-L jumpered) |
15 Hz ±75 Hz per 1.0 A change |
Speed TrimRange |
± 200Hz |
Remote Variable Speed Range |
500 - 7.5 kHz |
Terminal Sensitivity J L N P |
100 Hz ±15 Hz/Volt@ 5.0 kΩ Impedance 735 Hz ±60 Hz/Volt@ 65.0 kΩ Impedance 148 Hz ±10 Hz/Volt@ 1 MΩ Impedance 10V DC Supply @ 20 mA MAX |
INPUT / OUTPUT |
|
DC Supply |
12V DC and24V DC Battery Systems Transient and Reverse Voltage Protected* |
Polarity |
Negative Ground(Case Isolated) |
Power Consumption |
50 mA continuous plus actuator current |
Speed Signal Range Speed Sensor Signal |
1.0 - 50 V AC 1.0 - 120 V RMS |
Actuator Current Range** (77°F (25°C)) |
Minimum 1.0 A Nominal 7.0 A Maximum 10.0 A |